Error CodeDescriptionPossible CausesMeasure to JudgeSolution
AL001AL001 Too many mem writingsFrequent parameter changes
Frequent parameter changes
Stop operating the controller or power off for 3 minutes
AL002AL002 Retain mem write errorFrequent parameter changesFrequent parameter changesStop operating the controller or power off for 3 minutes
AL003AL003 Inlet probe errorLoose wire/Wire break/Broken probeVisual inspectionConnect the wires tightly/ Reconnect the wire/ Replace the probe
AL004AL004 Outlet probe errorLoose wire/Wire break/Broken probeVisual inspectionConnect the wires tightly/ Reconnect the wire/ Replace the probe
AL005AL005 Ambient probe errorLoose wire/Wire break/Broken probeVisual inspectionConnect the wires tightly/ Reconnect the wire/ Replace the probe
AL006AL006 Condenser coil tempLoose wire/Wire break/Broken probeVisual inspectionConnect the wires tightly/ Reconnect the wire/ Replace the probe
AL007/AL137AL007 Water flow switchClogged filter, resulting in low flow rate
Low water flowClean filters
Air in pipes causing poor water flowLow water flowEvacuate pipeline and install automatic venting valve at the highest point of the system
 Water pump is not emptied, resulting in low flowLow water flowEmpty the water pump
Water system with valves closed or not fully openLow water flowOpen the valve
Water pump is too small, resulting in low flowLow water flowReplace the  water pump with a higher head flow rate
Water flow switch is brokenIf the above are ruled out, you can short the water flow switch and force the machine on. If the water outlet temperature is greater than the tank temperature of 8 degrees or more, continue the above operation. Within 5 degrees and no fault in the start-up, the water flow switch is broken.Replace the water flow switch
Water pump is brokenWater pump does not turnReplace water pumps
AL008AL008 Phase sequ.prot.alarmParameter setting exceptionsThree-phase unit reports faultSet DI5 on the Ot6 page inside M09 to Normally Open NO
AL013AL013 Low superheat - Vlv.ALong-term operation of the unit at low frequencies outside its operating rangeLong-term operation of the unit at a low frequency of 30HzChange the parameter of Alarm delay in the EEV n 1 page in M07 to 9999
AL028AL028 Battery discharge EVDStrong electrical interference with the unitReport a faultPower off for 3 minutes and then restart
AL037AL037 BLDC-alarm:Out of EnvelopeWater temperature too high or ambient temperature too lowAmbient or water temperature outside the permitted range of the unitOperates within the permitted operating range
AL038AL038 BLDC-alarm:Starting fail waitProgram errorCheck if the program version is up to dateBrush up on the latest programsBrush up on the latest programs
AL039AL039 BLDC-alarm:Starting fail exceededProgram errorCheck if the program version is up to dateBrush up on the latest programsBrush up on the latest programs
AL041/AL050AL041 BLDC-alarm:High discarge gas tempLack of refrigerantLow pressure is too low ausing high exhaustLeak check and repair then evacuate and fill with refrigerant according to the nameplate
Exhaust probe not sensing correctlyExhaust probe shows high or low even after shutdown更换排气探头
AL051/AL057/AL082/
AL051 Power+ alarm:01-OvercurrentLow supply voltageVoltage measured with multimeter in standby, 10% below rated voltageAdd a voltage regulator to keep the voltage stable, or provide a stable voltage, or thicken the power cable
Low voltage due to small wire diameterWhen the compressor is started and the voltage is measured with a multimeter, the voltage will slowly become lower and the voltage shown on the multimeter will be more than 10% below the rated voltageReplace suitable wire diameter
High current due to loose compressor or inverter wiringCheck if the power cable, compressor wiring, inverter inlet and outlet cables are loose and if there are burn marksRe-crimpe wire joints
Compressor coils short-circuitedExclude the above, measure the resistance between the three coil columns of the compressor two by two, there is a very small or large resistance, indicating that the compressor is badReplace Compressor
AL053AL053 Power+ alarm:03-DCbus overvoltageExcessive voltageActual voltage exceeds the rated by more than 20% under the measurementProvide stable supply voltage
AL054AL054 Power+ alarm:04-DCbus undervoltageVoltage too lowThe actual voltage is more than 25% below the rated voltage at the time of measurementProvide stable supply voltage
AL114AL114 Power+ alarm:Power+ offlineToo short an interval between power-off and power-up of the main unitRe-powering time less than 30 secondsPower off again and power back on after 3 minutes, if still not possible then power off for 10 minutes
Loose inverter connection cableScrews not tightenedRetighten
Inverter dipswitch in wrong positionThe four dip switches of the inverter are not oriented in the same directionRe-dial to Consistency
AL115AL115 EEV alarm:Low superheatLong-term operation of the unit at low frequencies outside its operating rangeLong-term operation of the unit at a low frequency of 30HzChange the parameter of Alarm delay in the EEV n 1 page in M07 to 9999
AL128AL128 Low press alarmSevere frosting of mainframe finsThe fins are covered in a very thick frostForced defrost, place the ambient probe as far away from the fins as possible to prevent it from being covered by snow and check for abnormal parameters
Insufficient airflow due to bad airfoilBroken wind bladesReplace wind blade
Refrigerant leakage from the systemThe low pressure is too low and oil leaks can be seen in the linesLeak check and repair then evacuate and fill with refrigerant according to the nameplate
Low pressure pressure sensor is brokenLow pressure gauge over 1kg, still reporting low pressure alarmReplace low pressure sensor
AL129AL129 High press alarmClogged filter, resulting in low flow

Difference in temperature between inlet and outlet water of more than 8 degreesClean filters
Air in the pipes, causing poor water flowDifference in temperature between inlet and outlet water of more than 8 degreesEvacuate pipeline and install automatic venting valve at the highest point of the system
Water pump not emptied, resulting in low flowDifference in temperature between inlet and outlet water of more than 8 degreesEmpty the water pump
Water system with valves closed or not fully openNo or low water flowOpen the valve
The hot water probe or underfloor heating probe is not placed in the corresponding return pipe or blind pipe of the water tankVery high water discharge temperature, over 60 degreesPlace the probe in the corresponding position
Pump head or flow rate too low, resulting in low flow rateDifference in temperature between inlet and outlet water of more than 8 degreesReplace the  water pump with a higher head flow rate
High pressure due to water-side heat exchanger foulingLow temperature difference between inlet and outlet water, high pressureCleaning of water-side heat exchanger with water treatment
High pressure due to air in the fluorine systemJittering of the high pressure gauge needleRe-vacuumine  and refill with refrigerant
Bad high voltage sensor switchPressure gauge does not exceed maximum pressure, but still reports high pressure alarmReplace the high-pressure pressure sensor
High pressure due to bad electronic expansion valveLow pressure is too low, and high pressure is too highReplace the electronic expansion valve
AL130AL130 Disc.temp.probe errorLoose wire/Wire break/Broken probeVisual inspectionConnect the wires tightly/ Reconnect the wire/ Replace the probe
AL131AL131 Suct.temp.probe errorLoose wire/Wire break/Broken probeVisual inspectionConnect the wires tightly/ Reconnect the wire/ Replace the probe
AL134AL134 Tank temp.probe errorLoose wire/Wire break/Broken probeVisual inspectionConnect the wires tightly/ Reconnect the wire/ Replace the probe
AL138AL138 High temp. alarmClogged filter, resulting in low flow
Water outlet temperature above 62 degreesClean filters
Air in the pipes, causing poor water flowWater outlet temperature above 62 degreesEvacuate pipeline and install automatic venting valve at the highest point of the system
Water pump not emptied, resulting in low flowWater outlet temperature above 62 degreesEmpty the water pump
Water system with valves not fully openWater outlet temperature above 62 degreesOpen the valve
Set temperature too high and flow rate too lowWater outlet temperature above 62 degreesReduce the setting temperature
Water pump too small, resulting in low flowWater outlet temperature above 62 degreesReplace the  water pump with a higher head flow rate
AL139AL139 Low temp. alarmClogged filter, resulting in low flow
Water outlet temperature below 5 degreesClean filters
Air in the pipes, causing poor water flowWater outlet temperature below 5 degreesEvacuate pipeline and install automatic venting valve at the highest point of the system
Water pump not emptied, resulting in low flowWater outlet temperature below 5 degreesEmpty the water pump
Water system with valves not fully openWater outlet temperature below 5 degreesOpen the valve
Set temperature too high and flow rate too lowWater outlet temperature below 5 degreesReduce the setting temperature
Water pump too small, resulting in low flowWater outlet temperature below 5 degreesReplace the  water pump with a higher head flow rate
AL153/AL154AL153 Fan1/2 faultFan drive dipswitch anomalyVisual inspectionFan drive dipswitch to be redialed, top left, bottom right
Loose wind turbine wiringCheck that the fan power socket is tightly plugged inPlug the fan connection socket firmly
Bad wind turbine driveVisual inspection of the power light does not illuminateReplace the fan drive
Broken motorManual rotation of the motor with jammingReplace the motor
AL155AL155 Fans OfflineFan drive dip switch abnormalVisual inspectionFan drive dipswitch to be redialed, top left, bottom right
Loose wind turbine wiringCheck that the fan power socket is tightly plugged inPlug the fan connection socket firmly
Wind turbine drive is brokenVisual inspection of the power light does not illuminateReplace the fan drive
Broken motorManual rotation of the motor with jammingReplace the motor



Abnormal Exclusion

Serial NumberAbnormal StatePossible CausesMeasure to JudgeTreatment Measures
1Unit does not operateThe machine is not switched onVisual inspectionWith hot water or heating symbols it is on
Loose linkage switchVisual inspectionShort the linkage switch
The machine is faultyVisual inspectionTroubleshooting
2Difficult to close AC contactorsVoltage too low or wire diameter too smallCheck the voltage with a multimeter and check the wire gaugeAdd a voltage regulator to keep the voltage stable
3Water pump running but water not circulating or noisy pumpWater system with airHands-on screeningWater system air discharge
Water system valves not fully openedVisual inspectionOpen the valve
Filters are dirty and cloggedHands-on screeningClean filters
4The room is not heatedHigh heat dissipation in a room with a lot of glass leads to an undersized machine configurationVisual inspectionIncreased configuration
The room is slow to heat up with humidityThe new house is rather dampWaiting for the room to dry
The room heats up slowly at first
Wait long enough for the room temperature to rise
Wet weather, resulting in frequent frost defrosting
Wait long enough for the room temperature to rise
5The compressor runs but the unit does not produce heatRefrigerant leaks
Leak check and repair then evacuate and fill with refrigerant according to the nameplate
Compressor damage
Leak check and repair then evacuate and fill with refrigerant according to the nameplate
Stuck four-way valve
Tap on the four-way valve body
6Defrost is not clean or does not go into defrostCoil probe dislodged
Place the coil probe into the probe clamp
Ambient probe covered in frost
Position the environmental probe on the fins as far away from the fins as possible
M10 inside the defrost ssetting parameters are inaccurate,so the unit can not enter the defrost.  The defrost conditions: 1 coil B9 temperature is lower than the M10 inside the Df04 page set value (default -1 degrees), 2 ambient temperature B3 minus the coil temperature B9 is greater than or equal to the set parameters M10 inside the Df05 page set value (default is 5), 3 ambient temperature B3 is less than or equal to the M10 inside the Df04 page set value (default 15 degrees), 4 defrost interval time reached (default 45 minutes)
Firstly, check the defrost parameter settings. If the parameters are correct, check whether the four entry conditions are met during normal operation of the unit. Then, adjust the parameters that are not met and allow the unit to enter the defrost. After defrosting, then make targeted adjustments.


Latest News & Articles

Related Heat Pump Articles

  • Why Does My Swimming Pool Heat Pump Freeze Up?

    2021-12-06

    During the winter season, some ice on your pool heat pump is a common occurrence. However, when the whole unit is covered in ice, there is a concern for worry as your device won't function well and might be at risk of getting damaged.This article focuses on people who want to use their pool heat pum Read More
  • A Complete Guide: Air Source Heat Pump Costs

    2022-01-07

    Heat pumps have surprisingly become a ‘necessary’ appliance for their ability to offer a convenient and reliable energy source for anyone looking to warm their pools or stay warm indoors. If you want to invest in a heating or cooling unit, heat pumps are undoubtedly a suitable option to suit your ne Read More
  • The Best Air Source Heat Pump Manufacturers of 2022

    2021-10-30

    Air source heat pumps are a highly efficient and renewable heating solution for many property owners. These valuable appliances help save money on energy bills, have a low carbon footprint, have a high Seasonal Coefficient of Performance (SCOP), can be utilized for heating and cooling, have low main Read More
  • Why choose an inverter heat pump to heat your pool?

    2021-11-30

    It's frustrating and uncomfortable to swim while the weather is a bit cold. With the weather shifts, temperatures can drop substantially, especially during cloudy days or winter. A significant drop in temperature can render a pool useless. About 90 % of pools in the U.S. are used two to three times Read More

Recommended Heat Pump Products

Air Source Monoblock Heat Pumps forHot Water/House Heatin

Guangzhou SPRSUN New Energy Technology Development Co., Ltd.

A Professional Heat Pump Manufacturer Since 1999
No.15 Tangxi Road, Yinsha lndustrial Park, Xintang, Zengcheng , Guangzhou, Guangdong, China, 511338

Contact SPRSUN. 7/24 Support. We Will Reply You ASAP!

Tel: 0086-20-82181867
Phone: 0086-18933985692